Chilled Water Fan Coil Unit: Complete Guide & Specs 2026

WELCOME TO OUR BLOG

We're sharing knowledgein the areas which fascinate us the most
click

Chilled Water Fan Coil Unit: Complete Guide & Specs 2026

Par Zoe-YESNCER August 3rd, 2026 47 vues
Chilled Water Fan Coil Unit: Complete Guide & Specs 2026

Chilled Water Fan Coil Unit: How It Works, Full Specifications & Selection Guide

A chilled water fan coil unit is the terminal device that decides whether a hydronic HVAC system actually delivers the comfort it was designed for. Get the sizing, coil configuration or control strategy wrong, and even a perfectly specified chiller plant will underperform. This guide covers how a chilled water FCU works, the complete technical specifications across concealed, cassette and exposed model families, and a practical selection process — written from the engineering data of a manufacturer that has built fan coil units since 2008.


How Does a Chilled Water Fan Coil Unit Work?

A chilled water fan coil unit transfers heat between room air and water circulating through a finned coil. Unlike a DX (direct expansion) unit, no refrigerant enters the occupied space — the refrigeration cycle stays entirely within the central chiller plant.

The operating sequence is straightforward:

  1. Chilled water supply. Water leaves the central chiller, typically at 7°C, and is pumped to the FCU coil.
  2. Air circulation. The unit's fan draws room air across the coil through a return grille.
  3. Heat exchange. Heat transfers from the warmer air into the cooler water flowing inside the copper tubes. Aluminium fins bonded to the tubes multiply the effective heat transfer surface.
  4. Dehumidification. When the coil surface drops below the air's dew point, moisture condenses onto the fins and drains away through the condensate pan — this is the latent cooling portion of the unit's capacity.
  5. Supply air delivery. Cooled, dehumidified air returns to the room; the warmed water (typically leaving at 12°C) returns to the chiller.

In heating mode the same coil circulates hot water instead — commonly 60°C in traditional boiler systems, or 45°C in low-temperature heat pump installations. This dual-mode capability is why hydronic fan coil units dominate hotel, hospital and commercial office projects across Europe and Asia.

Why the 45°C figure matters. As heat pumps replace gas boilers, supply water temperatures are falling. A coil sized only for 60°C water will deliver substantially less heat at 45°C. Any manufacturer serious about heat-pump-ready projects should publish capacity at both temperatures — a point worth checking on every datasheet you review.


Chilled Water FCU vs DX Fan Coil: Which Fits Your Project?

Criterion Chilled Water FCU DX Fan Coil
Cooling medium Water (7°C typical supply) Refrigerant
Refrigerant in occupied space None Yes
Best suited to Multi-zone buildings, 20+ terminal units Small buildings, single-zone
Central plant required Yes — chiller and pumps No — outdoor condensing unit
Pipe runs Long runs practical Limited by refrigerant line length
Simultaneous heat + cool Yes, with 4-pipe configuration Requires VRF system
Regulatory exposure (F-gas) Minimal at terminal level Higher
Typical application Hotels, hospitals, offices, apartments Retail units, small offices

For any project with more than roughly 20 terminal units, or where F-gas regulations create long-term compliance cost, chilled water systems generally win on both lifecycle economics and regulatory simplicity.


Complete Technical Specifications

Most manufacturer pages publish two or three figures. Below are the full performance tables across three product families, so your M&E engineer can size directly from this page.

Concealed Horizontal FCU — EC Motor Series

Variable-speed EC motors with adjustable static pressure from 0 to 50Pa. This is the standard specification for projects targeting energy compliance.

Model Cooling Cap. 7°C (kW) Heating Cap. 60°C (kW) Air Flow (m³/h) Power @12Pa (W) Power @30Pa (W) Power @50Pa (W) Noise @12Pa dB(A) Water Flow (m³/h)
FCU-02EC 1.8 3.49 360 14 19.8 26.3 18–32 0.4
FCU-03EC 3.26 5.27 545 16.7 24.3 32.4 18–30 0.59
FCU-04EC 3.97 6.77 724 22.4 32.5 42.5 20–34 0.73
FCU-05EC 4.6 8.65 900 32.9 43.5 55.7 23–38 0.81
FCU-06EC 5.75 11.17 1,090 52.1 67 82.2 29–43 1.0
FCU-08EC 7.45 13 1,440 60 78.5 98 28–42 1.2
FCU-10EC 9.19 15.97 1,750 72.8 92.2 115.9 32–43 1.57
FCU-12EC 10.8 17.7 2,140 92.7 116 155.5 33–44 1.86
FCU-14EC 12.7 21.2 2,490 125.2 156 186 37–47 2.19

Coil: 210mm height, 38.1mm width. Test conditions — cooling: chilled water in 7°C; heating: hot water in 60°C.

Concealed Horizontal FCU — AC Motor Series (9.52mm Copper Tube)

The cost-effective specification for residential and budget-sensitive commercial projects. Static pressure 30Pa.

Model Cooling Cap. 7°C (kW) Heating Cap. 60°C (kW) Air Flow (m³/h) Power Input (W) Noise dB(A) Water Flow (m³/h) Coil Length (mm)
FP-34WA 1.9 3.4 357 36 37 0.32 450
FP-51WA 2.8 5.18 535 50 39 0.478 580
FP-68WA 3.75 6.67 714 60 41 0.64 650
FP-85WA 4.6 7.5 892 74 43 0.797 760
FP-102WA 5.5 9.35 1,071 93 45 0.956 900
FP-136WA 7.3 12.4 1,428 130 47 1.275 1,100
FP-170WA 9.2 14.7 1,785 147 48 1.59 1,350
FP-204WA 11 17.6 2,090 183 50 1.9 1,550
FP-238WA 12.8 20.5 2,390 221 52 2.23 1,750

4-Way Cassette FCU — 2-Pipe

Ceiling-recessed units with RS485 master-slave control as standard; one unit can network up to 32 units. Static pressure 12Pa.

Model Cooling H (kW) Heating H (kW) Air Flow H (m³/h) Power (W) Noise dB(A) Water Flow (m³/h) W.P.D (kPa) Panel Size (mm)
FP-34KM 1.98 2.97 345 50 37 0.31 14 650×650
FP-51KM 2.98 4.8 510 50 39 0.46 14 650×650
FP-68KM 3.68 5.48 690 58 41 0.62 16 650×650
FP-85KM 4.98 7.2 875 72 43 0.77 18 800×800
FP-102KM 5.4 8.1 1,035 92 45 0.93 22 800×800
FP-136KM 7.2 10.8 1,375 126 46 1.24 25 800×800
FP-170KM 9.9 14.5 1,705 128 47 1.55 39 950×950
FP-204KM 10.8 16.2 2,045 152 49 1.86 44 950×950
FP-238KM 12.6 18.9 2,380 198 52 2.17 46 950×950

Test conditions — cooling: air inlet DB 27°C / WB 19.5°C; heating: air inlet DB 20°C. Water pipe in/out: ZG3/4" — DN20.

Exposed Design FCU — Aura Series

For projects where the unit is visible. Five-speed EC motor, zero static pressure.

Model Cooling Cap. Speed 5 (W) Heating 60°C Speed 5 (W) Heating 45°C Speed 5 (W) Air Flow Speed 5 (m³/h) Power Speed 5 (W) Noise Speed 1 dB(A) Noise Speed 5 dB(A) Unit Length (mm)
M2 1,660 2,680 1,664 330 14 21 37 850
M3 2,560 4,150 2,530 460 17 23 39 1,141
M4 3,420 5,440 3,320 590 19 24 41 1,332
M5 4,040 6,510 3,980 700 28 24 45 1,332

Aura efficiency ratings at High speed:

Model FCEER (W/W) FCCOP 60°C (W/W) FCCOP 45°C (W/W) Water Flow (m³/h) W.P.D (kPa)
M2 110 177 110 0.286 10.2
M3 141 229 139 0.441 6.7
M4 156 248 152 0.589 13.0
M5 124 200 122 0.695 17.2

2-Pipe vs 4-Pipe: Choosing Your Configuration

2-pipe systems circulate either chilled or hot water through a single coil, with the building switching seasonally between cooling and heating. Lower installation cost, simpler pipework, adequate for buildings with uniform load profiles.

4-pipe systems run separate chilled and hot water circuits, allowing one zone to cool while another heats. Essential for buildings with high internal gains on one facade and heat loss on another — common in mixed-use commercial developments.

Two 4-pipe coil arrangements are available:

Arrangement Cooling Cap. FP-102 (kW) Heating Cap. FP-102 (kW) Best for
3+1 (3 cooling rows, 1 heating row) 5.56 3.7 Cooling-dominant climates
2+2 (2 cooling rows, 2 heating rows) 3.8 5.7 Balanced or heating-dominant climates

Choose 3+1 where cooling load dominates and heating is a shoulder-season requirement. Choose 2+2 where both loads are substantial.


How to Select the Right Chilled Water FCU: 5 Steps

Step 1 — Calculate the room cooling load. Account for occupancy, lighting, equipment, solar gain through glazing, and fabric transmission. Do not size from floor area alone; a south-facing glazed office and an internal meeting room of identical size can differ by a factor of two.

Step 2 — Check the noise constraint before the capacity. This is the step most commonly reversed. Hotel guest rooms and hospital consultation rooms typically require below 30 dB(A). Once you fix that limit, only the fan speeds meeting it are available — and that determines which model sizes are genuinely usable. Selecting on capacity first and discovering the acoustic failure at commissioning is expensive.

Step 3 — Confirm the available static pressure. Ducted concealed units must overcome duct resistance, filters and grilles. Undersizing static pressure is a leading cause of airflow shortfall on site. EC motor units with 0–50Pa adjustable range provide commissioning headroom that fixed-speed AC units cannot.

Step 4 — Verify water-side hydraulics. Cross-check water flow rate and water pressure drop against your pump head calculation. A coil with excessive pressure drop in a long circuit can starve downstream units.

Step 5 — Match the installation format to the architecture. Concealed horizontal for suspended ceilings with duct space; cassette for exposed grid ceilings; ultra-thin concealed for retrofits with restricted plenum depth; exposed Aura or slim units where no ceiling void exists at all.


Maintenance Practices That Protect Capacity

Chilled water FCUs lose performance gradually and invisibly. Three maintenance items account for most of the degradation:

Filter replacement. A clogged filter reduces airflow, which reduces capacity and can cause coil freezing in low-load conditions. Quarterly inspection in commercial environments; monthly in high-dust settings.

Coil cleaning. Fin surfaces accumulate dust that acts as thermal insulation. Annual cleaning restores heat transfer; neglected coils can lose 10–20% of rated capacity.

Condensate drain inspection. Blocked drain pans cause water damage and microbial growth. Check before each cooling season and confirm the pan falls correctly to the drain point.

Water quality. Corrosion inhibitor levels and system water chemistry deserve annual testing. Poor water quality damages coils from the inside, where inspection is impossible.


Why Yesncer Chilled Water Fan Coil Units

Every performance figure on this page is generated in-house. Yesncer operates a national-level enthalpy difference performance laboratory, a semi-anechoic chamber for acoustic measurement, a -30°C ultra-low temperature enthalpy difference testing laboratory, and a salt spray test room for corrosion durability validation. When your consulting engineer requests raw test data to validate a specification, it is available.

  • 35 years of heating and cooling manufacturing since 1986; dedicated FCU production since 2008
  • 40,000㎡ production facility with 500,000 units annual capacity
  • 15,000㎡ finished-goods warehouse supporting confirmed delivery schedules
  • 60+ countries served, with CE, CRAA and ISO9001 certification
  • 40-person R&D team with 3D printing prototyping for rapid custom sampling
  • 24-hour technical response, with replacement or compensation on confirmed quality failures

Frequently Asked Questions

What is the difference between a chilled water fan coil unit and a hydronic fan coil unit? They describe the same equipment. "Hydronic" refers to the water-based heat transfer medium; "chilled water" specifies the cooling function. A hydronic fan coil unit running hot water in winter and chilled water in summer is simply a chilled water FCU operating in both modes.

Can a chilled water fan coil unit provide heating? Yes. The same coil circulates hot water for heating. Capacity depends on supply temperature — for example, the Aura M4 delivers 5,440W at 60°C water and 3,320W at 45°C. Always check the datasheet at the temperature your plant will actually deliver, particularly on heat pump projects.

What is the typical chilled water supply temperature? 7°C supply with 12°C return is the industry standard design condition, giving a 5K temperature difference across the coil. Some low-energy designs use elevated supply temperatures of 10–14°C to improve chiller efficiency, which reduces both sensible and latent capacity — coils must be resized accordingly.

How do I know whether to choose an AC or EC motor unit? Choose EC where energy regulations apply, where the unit runs long hours, or where low noise matters — EC units offer variable speed, lower power draw and adjustable static pressure. Choose AC where first cost dominates and operating hours are limited. The FCU-02EC draws 14W at 12Pa; a comparable AC unit draws 36W.

What noise level should I specify for a hotel guest room? Most 4- and 5-star hotel specifications require below 30 dB(A) in the occupied space at the operating fan speed. Units must be selected at a speed that meets this, not at maximum speed. The Aura M2 produces 21 dB(A) at Speed 1 and 22 dB(A) at Speed 2, leaving genuine headroom.

How often should filters be replaced? Quarterly in standard commercial environments; monthly in high-dust conditions such as construction-adjacent sites or industrial settings. Filter condition directly affects both airflow and delivered capacity.

Do you supply OEM or private-label fan coil units? Yes. Yesncer operates an established OEM/ODM programme covering panel finish and colour, brand logo and labelling, control interface options, coil configuration and export packaging, supported by a 40-person R&D team and rapid prototyping.


Request Technical Documentation

Specifying chilled water fan coil units for an upcoming project?

  • Full technical datasheets — every series, every model, every fan speed
  • CE and CRAA certification documents — available immediately on request
  • Project-specific selection support from our engineering team
  • OEM programme details including MOQ and lead times

[Download Full Specification Sheet (PDF) →] [Request Project Selection Support →] [Contact Our Engineering Team →]

Top FCU Manufacturer for Global Distributors & Contractors | Yesncer Official
La page précédente
Top FCU Manufacturer for Global Distributors & Contractors | Yesncer Official
En savoir plus
La page suivante
Chilled Water vs DX Fan Coil Unit: Which to Specify 2026
En savoir plus

REQUEST MORE DETAILS

Please fill out the form below and click the button to request more information about
FirstName *
Email *
Mobile
Message *
Leave a message
FirstName *
Email *
Mobile
Message *
Nous utilisons des Cookie pour améliorer votre expérience en ligne. En poursuivant votre navigation sur ce site, nous supposons que vous acceptez notre utilisation des Cookie.